American Power Conversions

Back-UPS Pro 1100


APC UPS

Features
  • APC Back-UPS Pro
  • 1100VA/670W
  • Input 120V/Output 120V
  • Interface Port DB-9 RS-232
  • Lightning and Surge Protection
  • Overload Indicator
  • Replace Battery Indicator
  • Resettable circuit breaker
  • User Manual



  • Product Specifications
  • Interface port: DB-9 RS-232
  • Control panel: LED status display with On Line: On Battery: Replace Battery and Overload indicators
  • Audible alarm: Alarm when on battery : distinctive low battery alarm: overload continuous tone alarm
  • Output power capacity: 1,000 VA
  • Output power capacity: 670 Watts
  • Nominal output voltage: 120 V
  • Waveform type: Stepped approximation to a sinewave
  • Output Connections: (6)NEMA 5-15R
  • Nominal input voltage: 120 V
  • Input frequency: 50/60 Hz +/- 3 Hz (auto sensing)
  • Typical backup time: at half load 18.6 minutes (335 Watts)
  • Typical backup time: at full load 6.6 minutes (670 Watts)
  • Battery type: Maintenance-free sealed Lead-Acid battery with suspended electrolyte: leakproof
  • Typical recharge time**: 3 hour(s)
  • Input Connection Type: NEMA 5-15P
  • Cord Length: 6'
  • Input voltage range for main operations: 88 - 148V
  • Surge energy rating: 320 joules
  • Filtering: Full time multi-pole noise filtering: 0.3% IEEE surge let-through: zero clamping response time: meets UL 1449
  • Dataline protection: RJ-45 Modem/Fax/DSL/10-100 Base-T protection
  • Approvals: CSA, FCC Part 15 Class B, FCC Part 68, UL 1778
  • Operating Environment: 0 - 40 °C (32 - 104°F)
  • Operating Relative Humidity: 0 - 95%
  • Operating Elevation: 0-10000 feet (0-3000 m)
  • Storage Temperature: -15 - 45 °C (5 - 113°F)
  • Storage Relative Humidity: 0 - 95% Non-condensing
  • Storage Elevation: 0-50000 feet (0-15000 m)
  • Audible noise at 1 meter from surface of unit: 50 dBA
  • Color: Beige
  • Dimensions: 8.5"H x 6.7"W x 17.3"D
  • Weight: 42.60 lbs.

    **The time to recharge to 90% of full battery capacity following a discharge to shutdown using a load rated for 1/2 the full load rating of the UPS.